Description

Functions:
1.Over-voltage protection
2.Under-voltage protection
3.Over-current protection
4.Automatic recovery
5.Voltage display(voltage measurement)
6.Current display (current measurement)
7. Voltage calibration: Voltage +-10% adjustable. A13
8. Restore factory settings: press the down button for more than 12s
9.Fault inquiry: Press the UP button from more than 12S
Product Parameters:  
1.Model number:TOVPD1-60-EC
2.Power supply:230VAC 50/60Hz
3.Max.Loading power:1~40A  Adjustable(default:40A)
                                    1~63A  Adjustable(default:63A)
4.Over-voltage protection value range:230V~300~OFF(default:270V)
 Over-voltage recovery voltage range:225V–295V(default:250V)
   Over-voltage protection action time:0.1s~30s(default value:0.5s)
Over-voltage recovery delay time:1s~500s(default:30s)
5.Under-voltage protection value range:140V–210V –OFF(default:170V)
 Under-voltage recovery voltage range:145V–215V (default:190V)
   Under-voltage protection action time:0.1s~30s(default:0.5s)
   Under-voltage recovery delay time:1s~500s(default:30s)
6.Over-current adjustment range:1-40A (default:20A)1-63A (default:40A)
   Over-current action range:0.1~30 second (default:0.5s)
Over-currentrecovery delay time:1s~500s(default:30s)
7.Power-on delay time:1s~500s(default:10s)
9.Power consumption : <2W
10.Electric machinery life : 100,000 times
11.Installation:35mm DIN rail
 
110V Version
2.Power supply:110VAC 50/60Hz
3.Max.Loading power:1~63A Adjustable(default:63A)
4.Over-voltage protection value range:80V~300~OFF(default:145V)
Over-voltage recovery voltage range:75V–295V(default:140V)
Over-voltage protection action time:0.1s~30s(default value:0.5s)
Over-voltage r ecovery delay time:1s~500s(default:30s)
5.Under-voltage protection value range:80V–300V –OFF(default:90V)
Under-voltage recovery voltage range:85V–305V (default:95V)
Under-voltage protection action time:0.1s~30s(default:0.5s)
Under-voltage r ecovery delay time:1s~500s(default:30s)
6.Over-current adjustment range:1-63A (default:40A)
Over-current action range:0.1~30 second (default:0.5s)
Over-current r ecovery delay time:1s~500s(default:30s)
7.Power-on delay time:1s~500s(default:10s)
8.Power consumption : <2W
9.Electric machinery life : 100,000 times
10.Installation:35mm DIN rail